Schneider Electric charging stations
Supported Devices
| Device Type | Variants | Modbus TCP (Ethernet) | RS485 |
|---|---|---|---|
| EVlink Pro AC | GEX Series | ✅ | ❌ |

Connection
The communication between the a-TroniX Controller and the Schneider charging station takes place via Modbus TCP.
- Connect the charging station to the same local network (LAN) as the Controller using an Ethernet cable.
- For correct ethernet wiring standards, follow the guidelines for ethernet wiring.
Configuration
To allow the a-TroniX Controller to control the station, you must enable Modbus TCP via the eSetup for Electrician app or the charger's web interface.
- Log in to the charger using the eSetup app.
- Go to the Network settings and assign a Static IP address to the charger. This ensures the Controller can always find it.
- Go to Communication (or Backend) settings.
- Set Modbus TCP to Enable.
- Ensure the Port is set to 502.
- Save the settings and reboot the charger if prompted.
Warning
Warning
Make sure the Modbus Slave ID is set to 1 (or between 1 and 247). The default address is usually 1 or 255.
Adding to the Controller
- Go to the a-TroniX Controller web interface.
- Navigate to Devices > Add Device.
- Select Schneider > Modbus TCP.
- Enter the IP Address you configured in the charger.
- Enter Port 502.
- Click Scan.