Nibe

Nibe Heatpump F-Series

Supported Devices

Device TypeModbus TCP (Ethernet)RS485
Nibe F-Series Heatpump❌✅
Note
Note

The Modbus 40 communication module is also needed to enable Modbus communication on this heatpump https://www.nibe.eu/nl-nl/producten/accessoires/modbus-40

[!WARNING] Control is only possible using SG-Ready Operation Modes (Boosting or Blocking). Specific Wattage control is not supported. The control is done by using the offset curve of the manufacturer

Connection

The communication between the a-TroniX Controller and the Nibe F1253 heatpump operates via RS485.

RS485

Info
RS485 Wiring
  • For correct RS485 wiring: Follow the guidelines for RS485 wiring.
  • If the wiring shown in the table below is incorrect, please let us know.
  • There is no general consensus in the industry about the usage of A and B for the RS485 polarity, so it may be counterintuitive and opposite of what you might expect for some devices.
Devicea-TroniX Controller model OM1a-TroniX Controller model IG8RS485-USB converterRS485-Ethernet converter
ARS485 ARS485_POSRS485 ATX+
BRS485 BRS485_NEGRS485 BTX-
GND (if available)RS GNDGNDNot availableG
Last updated December 10, 2025Edit this page